inosakiInosakiinosaki

Contact Us
sales@365accountings.com   

SIMATIC ET 200SP – SIPLUS Extreme RAIL Interface Modules – Siemens

USD $ 185.01USD $ 190.89

SKU: N/A
SIPLUS ET 200SP IM 155-6PN ST (BA) TX RAIL

The SIPLUS ET 200SP IM 155-6PN ST (BA) TX RAIL is designed mainly for standard PROFINET applications with average station expansion of up to 32 modules (max. 512 IO signals). All I/O modules, including PROFIsafe, can be used. In addition, the station can be expanded with as many as 16 IP67 modules of the SIMATIC ET 200AL series using BA-Send/BU-Send.

SIPLUS ET 200SP IM 155-6PN HF T1/TX RAIL

The SIPLUS ET 200SP IM 155-6PN HF T1 RAIL/ET 200SP IM 155-6PN HF TX RAIL are designed mainly for PROFINET applications with a high, flexible demand for functions, as well as large station expansion of up to 64 modules (max. 1024 IO signals). All I/O modules, including PROFIsafe, can be used. In addition, the station can be expanded with as many as 16 IP67 modules of the SIMATIC ET 200AL series using BA-Send/BU-Send.

Siemens Modules ET-200SP Product Specifications:

Article number6AG2155-6AA01-4BN06AG2155-6AU01-4BN06AG2155-6AU01-1CN06AG2155-6AU01-4CN0
SIPLUS ET 200SP IM155-6PN ST BA TX RAILSIPLUS ET 200SP IM155-6PN ST TX RAILSIPLUS ET 200SP IM155-6PN HF T1 RAILSIPLUS ET 200SP IM155-6PN HF TX RAIL
General information
Product type designationIM 155-6 PN STIM 155-6 PN STIM 155-6 PN/2 HFIM 155-6 PN/2 HF
Firmware version
● FW update possibleYesYes
Product function
● I&M dataYes; I&M0 to I&M3Yes; I&M0 to I&M3Yes; I&M0 to I&M3Yes; I&M0 to I&M3
● Module swapping during operation (hot swapping)Yes; Single hot swappingYes; Single hot swappingYes; Multi-hot swappingYes; Multi-hot swapping
● Isochronous modeNoNoYesYes
● Tool changerYes; Docking station and docking unitYes; Docking station and docking unit
● Local coupling, IO dataNoNo
● Local coupling, data recordsNoNo
Engineering with
● STEP 7 TIA Portal configurable/integrated from versionsee entry ID: 109746275see entry ID: 109746275see entry ID: 109746275see entry ID: 109746275
Configuration control
via datasetYesYesYesYes
Supply voltage
Rated value (DC)24 V24 V24 V24 V
permissible range, lower limit (DC)19.2 V19.2 V19.2 V19.2 V
permissible range, upper limit (DC)28.8 V28.8 V28.8 V28.8 V
Reverse polarity protectionYesYesYesYes
Short-circuit protectionYesYes
Mains buffering
● Mains/voltage failure stored energy time10 ms10 ms10 ms10 ms
Input current
Current consumption (rated value)450 mA450 mA
Current consumption, max.550 mA550 mA700 mA700 mA
Inrush current, max.3.7 A3.7 A4.5 A4.5 A
I²t0.09 A²·s0.09 A²·s0.25 A²·s0.25 A²·s
Power
Infeed power to the backplane bus4.5 W4.5 W
Power loss
Power loss, typ.1.9 W1.9 W2.4 W2.4 W
Address area
Address space per module
● Address space per module, max.256 byte; per input / output256 byte; per input / output288 byte; For input and output data respectively288 byte; For input and output data respectively
Address space per station
● Address space per station, max.512 byte; Dependent on configuration512 byte; Dependent on configuration1 440 byte; Dependent on configuration1 440 byte; Dependent on configuration
Hardware configuration
Rack
● Modules per rack, max.32; + 16 ET 200AL modules32; + 16 ET 200AL modules64; + 16 ET 200AL modules64; + 16 ET 200AL modules
Submodules
● Number of submodules per station, max.256256256256
Time stamping
Accuracy10 ms10 ms
Interfaces
Number of PROFINET interfaces1; 2 ports (switch)1; 2 ports (switch)1; 2 ports (switch)1; 2 ports (switch)
1. Interface
Interface types
● RJ 45 (Ethernet)Yes; Pre-assembled BusAdapter BA 2x RJ45
● Number of ports222; via BusAdapter2; via BusAdapter
● integrated switchYesYesYesYes
● BusAdapter (PROFINET)Yes; Applicable BusAdapter: BA 2x RJ45, BA 2x FCYes; Applicable BusAdapter: BA 2x RJ45, BA 2x FCYes; Compatible BusAdapter: BA 2x RJ45, BA 2x FC, BA 2x SCRJ, BA SCRJ / RJ45, BA SCRJ / FC, BA 2x LC, BA LC / RJ45, BA LC / FCYes; Compatible BusAdapter: BA 2x RJ45, BA 2x FC, BA 2x SCRJ, BA SCRJ / RJ45, BA SCRJ / FC, BA 2x LC, BA LC / RJ45, BA LC / FC
Protocols
● PROFINET IO DeviceYesYesYesYes
● Open IE communicationYesYesYesYes
● Media redundancyYes; PROFINET MRPYes; PROFINET MRPYes; PROFINET MRPYes; PROFINET MRP
Interface types
RJ 45 (Ethernet)
● Transmission procedurePROFINET with 100 Mbit/s full duplex (100BASE-TX)PROFINET with 100 Mbit/s full duplex (100BASE-TX)PROFINET with 100 Mbit/s full duplex (100BASE-TX)PROFINET with 100 Mbit/s full duplex (100BASE-TX)
● 10 MbpsYes; for Ethernet servicesYes; for Ethernet servicesNoNo
● 100 MbpsYes; PROFINET with 100 Mbit/s full duplex (100BASE-TX)Yes; PROFINET with 100 Mbit/s full duplex (100BASE-TX)Yes; PROFINET with 100 Mbit/s full duplex (100BASE-TX)Yes; PROFINET with 100 Mbit/s full duplex (100BASE-TX)
● AutonegotiationYesYesYesYes
● AutocrossingYesYesYesYes
Protocols
Number of connections
● Number of MtM communication relationships/connections, max.1616
PROFINET IO Device
Services
— IRTYes; with send cycles of between 250 µs and 4 ms in increments of 125 µsYes; with send cycles of between 250 µs and 4 ms in increments of 125 µsYes; 250 μs, 500 μs, 1 ms, 2 ms, 4 ms additionally with IRT with high performance: 250 µs to 4 ms in 125 µs frameYes; 250 μs, 500 μs, 1 ms, 2 ms, 4 ms additionally with IRT with high performance: 250 µs to 4 ms in 125 µs frame
— PROFIenergyYesYesYesYes
— Prioritized startupYesYesYesYes
— Shared deviceYesYesYesYes
— Number of IO Controllers with shared device, max.2244
Redundancy mode
● PROFINET system redundancy (S2)NoNoYes; NAP S2Yes; NAP S2
● Redundant PROFINET configuration (R1)NoNo
● H-Sync forwardingYesYes
Media redundancy
— MRPYesYesYesYes
— MRPDNoNoNoNo
Open IE communication
● TCP/IPYesYesYesYes
● SNMPYesYesYesYes
● LLDPYesYesYesYes
Isochronous mode
EquidistanceYesYes
shortest clock pulse250 µs250 µs
max. cycle4 ms4 ms
Bus cycle time (TDP), min.250 µs250 µs
Jitter, max.1 µs1 µs
Interrupts/diagnostics/status information
Status indicatorYesYesYesYes
AlarmsYesYesYesYes
Diagnostics functionYesYesYesYes
Diagnostics indication LED
● RUN LEDYes; green LEDYes; green LEDYes; green LEDYes; green LED
● ERROR LEDYes; red LEDYes; red LEDYes; red LEDYes; red LED
● MAINT LEDYes; Yellow LEDYes; Yellow LEDYes; Yellow LEDYes; Yellow LED
● Monitoring of the supply voltage (PWR-LED)Yes; green PWR LEDYes; green PWR LEDYes; green PWR LEDYes; green PWR LED
● Connection display LINK TX/RXYes; 2x green link LEDs on BusAdapterYes; 2x green link LEDs on BusAdapterYes; 2x green link LEDs on BusAdapterYes; 2x green link LEDs on BusAdapter
Potential separation
between backplane bus and electronicsNoNoNoNo
between PROFINET and all other circuitsYes; 1 500 V ACYes; 1 500 V ACYesYes
between supply and all other circuitsNoNoNoNo
Permissible potential difference
between different circuitsSafety extra low voltage SELVSafety extra low voltage SELV
Isolation
Isolation tested with750 V DC (type test) and according to EN 50155 (routine test)750 V DC (type test) and according to EN 50155 (routine test)750 V DC (type test) and according to EN 50155 (routine test)750 V DC (type test) and according to EN 50155 (routine test)
Standards, approvals, certificates
Network loading class2233
Security levelAccording to Security Level 1 Test Cases V1.1.1According to Security Level 1 Test Cases V1.1.1According to Security Level 1 Test Cases V1.1.1According to Security Level 1 Test Cases V1.1.1
Railway application
● EN 50121-3-2Yes; EMC for rail vehiclesYes; EMC for rail vehiclesYes; EMC for rail vehiclesYes; EMC for rail vehicles
● EN 50121-4Yes; EMC for signal and telecommunications systemsYes; EMC for signal and telecommunications systemsYes; EMC for signal and telecommunications systemsYes; EMC for signal and telecommunications systems
● EN 50124-1Yes; Railway applications – overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DCYes; Railway applications – overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DCYes; Railway applications – overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DCYes; Railway applications – overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DC
● EN 50125-1Yes; Rail vehicles – see ambient conditionsYes; Rail vehicles – see ambient conditionsYes; Rail vehicles – see ambient conditionsYes; Rail vehicles – see ambient conditions
● EN 50125-2Yes; Stationary electrical equipment – see ambient conditionsYes; Stationary electrical equipment – see ambient conditionsYes; Stationary electrical equipment – see ambient conditionsYes; Stationary electrical equipment – see ambient conditions
● EN 50125-3Yes; Signal and telecommunications systems – see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track)Yes; Signal and telecommunications systems – see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track)Yes; Signal and telecommunications systems – see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track)Yes; Signal and telecommunications systems – see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track)
● EN 50155Yes; Rail vehicles – temperature class OT4, ST1/ST2, horizontal mounting positionYes; Rail vehicles – temperature class OT4, ST1/ST2, horizontal mounting positionYes; Rail vehicles – temperature class OT1, ST1/ST2, horizontal mounting positionYes; Rail vehicles – temperature class OT4, ST1/ST2, horizontal mounting position
● EN 61373Yes; Rail vehicles – vibrations and shocks: Category 1 Class A/BYes; Rail vehicles – vibrations and shocks: Category 1 Class A/BYes; Rail vehicles – vibrations and shocks: Category 1 Class A/BYes; Rail vehicles – vibrations and shocks: Category 1 Class A/B
● Fire protection acc. to EN 45545-2Yes; For proof of conformity, see Service & SupportYes; For proof of conformity, see Service & SupportYes; For proof of conformity, see Service & SupportYes; For proof of conformity, see Service & Support
Ambient conditions
Ambient temperature during operation
● horizontal installation, min.-40 °C; = Tmin (incl. condensation/frost)-40 °C; = Tmin (incl. condensation/frost)-30 °C; = Tmin (incl. condensation/frost)-40 °C; = Tmin (incl. condensation/frost)
● horizontal installation, max.70 °C; = Tmax; +85 °C for 10 min (OT4, ST1/ST2 acc. to EN 50155)70 °C; = Tmax; +85 °C for 10 min (OT4, ST1/ST2 acc. to EN 50155)60 °C; = Tmax; +70 °C for 10 min (OT1, ST1/ST2 acc. to EN 50155)70 °C; = Tmax; +85 °C for 10 min (OT4, ST1/ST2 acc. to EN 50155)
● vertical installation, min.-40 °C; = Tmin-40 °C; = Tmin-30 °C; = Tmin-40 °C; = Tmin
● vertical installation, max.50 °C; = Tmax50 °C; = Tmax50 °C; = Tmax50 °C; = Tmax
Altitude during operation relating to sea level
● Installation altitude above sea level, max.2 000 m2 000 m2 000 m2 000 m
● Ambient air temperature-barometric pressure-altitudeTmin … Tmax at 1 140 hPa … 795 hPa (-1 000 m … +2 000 m)Tmin … Tmax at 1 140 hPa … 795 hPa (-1 000 m … +2 000 m)Tmin … Tmax at 1 140 hPa … 795 hPa (-1 000 m … +2 000 m)Tmin … Tmax at 1 140 hPa … 795 hPa (-1 000 m … +2 000 m)
Relative humidity
● With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation
Resistance
Coolants and lubricants
— Resistant to commercially available coolants and lubricantsYes; Incl. diesel and oil droplets in the airYes; Incl. diesel and oil droplets in the airYes; Incl. diesel and oil droplets in the airYes; Incl. diesel and oil droplets in the air
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on requestYes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on requestYes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on requestYes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *Yes; Class 3S4 incl. sand, dust, *Yes; Class 3S4 incl. sand, dust, *Yes; Class 3S4 incl. sand, dust, *
— Against mechanical environmental conditions acc. to EN 60721-3-3Yes; Class 3M8 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)Yes; Class 3M8 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)Yes; Class 3M8 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Use on land craft, rail vehicles and special-purpose vehicles
— to biologically active substances according to EN 60721-3-5Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on requestYes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on requestYes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on requestYes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request
— to chemically active substances according to EN 60721-3-5Yes; Class 5C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *Yes; Class 5C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *Yes; Class 5C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *Yes; Class 5C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-5Yes; Class 5S3 incl. sand, dust; *Yes; Class 5S3 incl. sand, dust; *Yes; Class 5S3 incl. sand, dust; *Yes; Class 5S3 incl. sand, dust; *
— Against mechanical environmental conditions acc. to EN 60721-3-5Yes; Class 5M2 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)Yes; Class 5M2 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)Yes; Class 5M2 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
— against mechanical environmental conditions in agriculture acc. to ISO 15003Yes; level 1 (Location LE) using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)Yes; level 1 (Location LE) using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)Yes; level 1 (Location LE) using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Usage in industrial process technology
— Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)Yes; Class 3 (excluding trichlorethylene)Yes; Class 3 (excluding trichlorethylene)Yes; Class 3 (excluding trichlorethylene)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!* The supplied plug covers must remain in place over the unused interfaces during operation!* The supplied plug covers must remain in place over the unused interfaces during operation!* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
● Coatings for printed circuit board assemblies acc. to EN 61086Yes; Class 2 for high reliabilityYes; Class 2 for high reliabilityYes; Class 2 for high reliabilityYes; Class 2 for high reliability
● Protection against fouling acc. to EN 60664-3Yes; Type 1 protectionYes; Type 1 protectionYes; Type 1 protectionYes; Type 1 protection
● Electronic equipment on rolling stock acc. to EN 50155Yes; Class PC2 protective coating acc. to EN 50155:2017Yes; Class PC2 protective coating acc. to EN 50155:2017Yes; Class PC2 protective coating acc. to EN 50155:2017Yes; Class PC2 protective coating acc. to EN 50155:2017
● Military testing according to MIL-I-46058C, Amendment 7Yes; Discoloration of coating possible during service lifeYes; Discoloration of coating possible during service lifeYes; Discoloration of coating possible during service lifeYes; Discoloration of coating possible during service life
● Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal coating, Class AYes; Conformal coating, Class AYes; Conformal coating, Class AYes; Conformal coating, Class A
connection method / header
ET-Connection
● via BU/BA SendYes; + 16 ET 200AL modulesYes; + 16 ET 200AL modulesYes; + 16 ET 200AL modulesYes; + 16 ET 200AL modules
Mechanics/material
Strain reliefYes; OptionalYes; Optional
Dimensions
Width50 mm50 mm50 mm50 mm
Height117 mm117 mm117 mm117 mm
Depth74 mm74 mm74 mm74 mm
Weights
Weight, approx.190 g; IM 155-6 PN BA with 2x RJ45 ports and server module147 g; without BusAdapter120 g; without BusAdapter120 g; without BusAdapter
Other
Note:for use in railway applications, also observe the product information “SIPLUS extreme RAIL” A5E37661960A, Online Support article 109736776for use in railway applications, also observe the product information “SIPLUS extreme RAIL” A5E37661960A, Online Support article 109736776for use in railway applications, also observe the product information “SIPLUS extreme RAIL” A5E37661960A, Online Support article 109736776for use in railway applications, also observe the product information “SIPLUS extreme RAIL” A5E37661960A, Online Support article 109736776
WeightN/A
DimensionsN/A