inosakiInosakiinosaki

Contact Us
sales@365accountings.com   

SIMATIC S7-1500 – SM534 Analog Input/Output Module AI 4x U/I/R/RTD/TC ST – Siemens Analog Modules

USD $ 731.55

SKU: 6ES7534-7QE00-0AB0

Analog inputs record process signals such as pressure or temperature and forward them in digitalized format (16-bit format) to the control. They are suitable for the measurement of current (2-wire and 4-wire transmitters), voltage, and resistance, as well as for the connection of resistance thermometers and thermocouples (measurement types depend on the module). Analog outputs convert a 16-bit digital value into a current or a voltage and output this to the process. They are suitable, for example, for controlling proportional valves or small servo drives.

The following analog input/output module is available:

  • AI/AQ 4xU/I/RTD/TC / 2xU/I ST
    4 analog input channels;
    16 bit resolution; accuracy +/-0.3%; one potential group; 10 V common mode voltage; parameterizable diagnostics; hardware interrupts (two upper and lower limit values); calibration during execution time.
    2 output channels;
    16 bit resolution; accuracy +/-0.3%; one potential group; parameterizable diagnostics; parameterizable substitute values for the outputs; calibration during execution time.
    Module width 25 mm

Siemens Analog Modules S7-1500 Product Specifications:

Article number6ES7534-7QE00-0AB0
S7-1500, AI 4x U/I/RTD/TC/AQ 2x U/I ST
General information
Product type designationAI 4xU/I/RTD/TC /AQ 2xU/I ST
HW functional statusFrom FS01
Firmware versionV1.0.0
● FW update possibleYes
Product function
● I&M dataYes; I&M0 to I&M3
● Isochronous modeNo
● Prioritized startupNo
● Measuring range scalableNo
● Scalable measured valuesNo
● Adjustment of measuring rangeNo
● Output range scalableNo
Engineering with
● STEP 7 TIA Portal configurable/integrated from versionV13 / V13.0.2
● STEP 7 configurable/integrated from versionV5.5 SP3 / –
● PROFIBUS from GSD version/GSD revisionV1.0 / V5.1
● PROFINET from GSD version/GSD revisionV2.3 / –
Operating mode
● OversamplingNo
● MSIYes
● MSOYes
CiR – Configuration in RUN
Reparameterization possible in RUNYes
Calibration possible in RUNYes
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Input current
Current consumption, max.200 mA
Encoder supply
24 V encoder supply
● Short-circuit protectionYes
● Output current, max.20 mA; Max. 47 mA per channel for a duration < 10 s
Power
Power available from the backplane bus0.7 W
Power loss
Power loss, typ.3.3 W
Analog inputs
Number of analog inputs4
● For current measurement4
● For voltage measurement4
● For resistance/resistance thermometer measurement2
● For thermocouple measurement4
permissible input voltage for voltage input (destruction limit), max.28.8 V
permissible input current for current input (destruction limit), max.40 mA
Constant measurement current for resistance-type transmitter, typ.150 Ohm, 300 Ohm, 600 Ohm, Pt100, Pt200, Ni100: 1.25 mA; 6 000 Ohm, Pt500, Pt1000, Ni1000, LG-Ni1000: 0.625 mA; PTC: 0.472 mA
Technical unit for temperature measurement adjustableYes; °C/°F/K
Analog input with oversamplingNo
Standardization of measured valuesNo
Input ranges (rated values), voltages
● 0 to +5 VNo
● 0 to +10 VNo
● 1 V to 5 VYes
— Input resistance (1 V to 5 V)100 kΩ
● -1 V to +1 VYes
— Input resistance (-1 V to +1 V)10 MΩ
● -10 V to +10 VYes
— Input resistance (-10 V to +10 V)100 kΩ
● -2.5 V to +2.5 VYes
— Input resistance (-2.5 V to +2.5 V)10 MΩ
● -25 mV to +25 mVNo
● -250 mV to +250 mVYes
— Input resistance (-250 mV to +250 mV)10 MΩ
● -5 V to +5 VYes
— Input resistance (-5 V to +5 V)100 kΩ
● -50 mV to +50 mVYes
— Input resistance (-50 mV to +50 mV)10 MΩ
● -500 mV to +500 mVYes
— Input resistance (-500 mV to +500 mV)10 MΩ
● -80 mV to +80 mVYes
— Input resistance (-80 mV to +80 mV)10 MΩ
Input ranges (rated values), currents
● 0 to 20 mAYes
— Input resistance (0 to 20 mA)25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC
● -20 mA to +20 mAYes
— Input resistance (-20 mA to +20 mA)25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC
● 4 mA to 20 mAYes
— Input resistance (4 mA to 20 mA)25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC
Input ranges (rated values), thermocouples
● Type BYes
— Input resistance (Type B)10 MΩ
● Type CNo
● Type EYes
— Input resistance (Type E)10 MΩ
● Type JYes
— Input resistance (type J)10 MΩ
● Type KYes
— Input resistance (Type K)10 MΩ
● Type LNo
● Type NYes
— Input resistance (Type N)10 MΩ
● Type RYes
— Input resistance (Type R)10 MΩ
● Type SYes
— Input resistance (Type S)10 MΩ
● Type TYes
— Input resistance (Type T)10 MΩ
● Type UNo
● Type TXK/TXK(L) to GOSTNo
Input ranges (rated values), resistance thermometer
● Cu 10No
● Cu 10 according to GOSTNo
● Cu 50No
● Cu 50 according to GOSTNo
● Cu 100No
● Cu 100 according to GOSTNo
● Ni 10No
● Ni 10 according to GOSTNo
● Ni 100Yes; Standard/climate
— Input resistance (Ni 100)10 MΩ
● Ni 100 according to GOSTNo
● Ni 1000Yes; Standard/climate
— Input resistance (Ni 1000)10 MΩ
● Ni 1000 according to GOSTNo
● LG-Ni 1000Yes; Standard/climate
— Input resistance (LG-Ni 1000)10 MΩ
● Ni 120No
● Ni 120 according to GOSTNo
● Ni 200No
● Ni 200 according to GOSTNo
● Ni 500No
● Ni 500 according to GOSTNo
● Pt 10No
● Pt 10 according to GOSTNo
● Pt 50No
● Pt 50 according to GOSTNo
● Pt 100Yes; Standard/climate
— Input resistance (Pt 100)10 MΩ
● Pt 100 according to GOSTNo
● Pt 1000Yes; Standard/climate
— Input resistance (Pt 1000)10 MΩ
● Pt 1000 according to GOSTNo
● Pt 200Yes; Standard/climate
— Input resistance (Pt 200)10 MΩ
● Pt 200 according to GOSTNo
● Pt 500Yes; Standard/climate
— Input resistance (Pt 500)10 MΩ
● Pt 500 according to GOSTNo
Input ranges (rated values), resistors
● 0 to 150 ohmsYes
— Input resistance (0 to 150 ohms)10 MΩ
● 0 to 300 ohmsYes
— Input resistance (0 to 300 ohms)10 MΩ
● 0 to 600 ohmsYes
— Input resistance (0 to 600 ohms)10 MΩ
● 0 to 3000 ohmsNo
● 0 to 6000 ohmsYes
— Input resistance (0 to 6000 ohms)10 MΩ
● PTCYes
— Input resistance (PTC)10 MΩ
Thermocouple (TC)
Temperature compensation
— parameterizableYes
— internal temperature compensationYes
— external temperature compensation via RTDYes
— Compensation for 0 °C reference point temperatureYes; fixed value can be set
— Reference channel of the moduleNo
Cable length
● shielded, max.800 m; for U/I, 200 m for R/RTD, 50 m for TC
Analog outputs
Number of analog outputs2
Voltage output, short-circuit protectionYes
Voltage output, short-circuit current, max.24 mA
Current output, no-load voltage, max.22 V
Cycle time (all channels), min.3.2 ms; ±0.5 ms, regardless of the number of activated channels
Output ranges, voltage
● 0 to 10 VYes
● 1 V to 5 VYes
● -5 V to +5 VNo
● -10 V to +10 VYes
Output ranges, current
● 0 to 20 mAYes
● -20 mA to +20 mAYes
● 4 mA to 20 mAYes
Connection of actuators
● for voltage output two-wire connectionYes
● for voltage output four-wire connectionYes
● for current output two-wire connectionYes
Load impedance (in rated range of output)
● with voltage outputs, min.1 kΩ; 0.5 kOhm at 1 to 5 V
● with voltage outputs, capacitive load, max.1 µF
● with current outputs, max.750 Ω
● with current outputs, inductive load, max.10 mH
Cable length
● shielded, max.800 m; for current, 200 m for voltage
Analog value generation for the inputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max.16 bit
● Integration time, parameterizableYes
● Integration time (ms)2,5 / 16,67 / 20 / 100 ms
● Basic conversion time, including integration time (ms)9 / 23 / 27 / 107 ms
— additional conversion time for wire-break monitoring9 ms
— additional conversion time for resistance measurement150 ohm, 300 ohm, 600 ohm, Pt100, Pt200, Ni100: 2 ms, 6000 ohm, Pt500, Pt1000, Ni1000, LG-Ni1000, PTC: 4 ms
● Interference voltage suppression for interference frequency f1 in Hz400 / 60 / 50 / 10
● Time for offset calibration (per module)Basic conversion time of the slowest channel
Smoothing of measured values
● parameterizableYes
● Step: NoneYes
● Step: lowYes
● Step: MediumYes
● Step: HighYes
Analog value generation for the outputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max.16 bit
● Conversion time (per channel)0.5 ms
Settling time
● for resistive load1.5 ms
● for capacitive load2.5 ms
● for inductive load2.5 ms
Encoder
Connection of signal encoders
● for voltage measurementYes
● for current measurement as 2-wire transducerYes
— Burden of 2-wire transmitter, max.820 Ω
● for current measurement as 4-wire transducerYes
● for resistance measurement with two-wire connectionYes; Only for PTC
● for resistance measurement with three-wire connectionYes; All measuring ranges except PTC; internal compensation of the cable resistances
● for resistance measurement with four-wire connectionYes; All measuring ranges except PTC
Errors/accuracies
Linearity error (relative to input range), (+/-)0.02 %
Temperature error (relative to input range), (+/-)0.005 %/K; With TC type T 0.02 ± % / K
Crosstalk between the inputs, max.-80 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)0.02 %
Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-)0.02 %
Linearity error (relative to output range), (+/-)0.15 %
Temperature error (relative to output range), (+/-)0.002 %/K
Crosstalk between the outputs, max.-100 dB
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-)0.05 %
Temperature error of internal compensation±6 °C
note regarding accuracyat temperatures below 0 °C, the figures for operating error and temperature error are doubled
Operational error limit in overall temperature range
● Voltage, relative to input range, (+/-)0.3 %
● Current, relative to input range, (+/-)0.3 %
● Resistance, relative to input range, (+/-)0.3 %
● Resistance thermometer, relative to input range, (+/-)0.3 %; Ptxxx standard: ±1.5 K, Ptxxx climate: ±0.5 K, Nixxx standard: ±0.5 K, Nixxx climate: ±0.3 K
● Thermocouple, relative to input range, (+/-)0.3 %; Type B: > 600 °C ±4.6 K, type E: > -200 °C ±1.5 K, type J: > -210 °C ±1.9 K, type K: > -200 °C ±2.4 K, type N: > -200 °C ±2.9 K, type R: > 0 °C ±4.7 K, type S: > 0 °C ±4.6 K, type T: > -200 °C ±2.4 K
● Voltage, relative to output range, (+/-)0.3 %
● Current, relative to output range, (+/-)0.3 %
Basic error limit (operational limit at 25 °C)
● Voltage, relative to input range, (+/-)0.1 %
● Current, relative to input range, (+/-)0.1 %
● Resistance, relative to input range, (+/-)0.1 %
● Resistance thermometer, relative to input range, (+/-)0.1 %; Ptxxx standard: ±0.7 K, Ptxxx climate: ±0.2 K, Nixxx standard: ±0.3 K, Nixxx climate: ±0.15 K
● Thermocouple, relative to input range, (+/-)0.1 %; Type B: > 600 °C ±1.7 K, type E: > -200 °C ±0.7 K, type J: > -210 °C ±0.8 K, type K: > -200 °C ±1.2 K, type N: > -200 °C ±1.2 K, type R: > 0 °C ±1.9 K, type S: > 0 °C ±1.9 K, type T: > -200 °C ±0.8 K
● Voltage, relative to output range, (+/-)0.2 %
● Current, relative to output range, (+/-)0.2 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Series mode interference (peak value of interference < rated value of input range), min.40 dB
● Common mode voltage, max.10 V
● Common mode interference, min.60 dB
Interrupts/diagnostics/status information
Diagnostics functionYes
Substitute values connectableYes
Alarms
● Diagnostic alarmYes
● Limit value alarmYes; two upper and two lower limit values in each case
Diagnoses
● Monitoring the supply voltageYes
● Wire-breakYes; only for input type 1 … 5 V, 4 … 20 mA, TC, R, RTD and output type current
● Short-circuitYes; Only for output type “voltage”
● Overflow/underflowYes
Diagnostics indication LED
● RUN LEDYes; green LED
● ERROR LEDYes; red LED
● Monitoring of the supply voltage (PWR-LED)Yes; green LED
● Channel status displayYes; green LED
● for channel diagnosticsYes; red LED
● for module diagnosticsYes; red LED
Potential separation
Potential separation analog inputs
● between the channelsNo
● between the channels, in groups of4
● between the channels and backplane busYes
● Between the channels and load voltage L+Yes
Potential separation analog outputs
● between the channelsNo
● between the channels, in groups of2
● between the channels and backplane busYes
● Between the channels and load voltage L+Yes
Permissible potential difference
between the inputs (UCM)20 V DC
Between the inputs and MANA (UCM)10 V DC
between S- and MANA (UCM)8 V DC
Isolation
Isolation tested with707 V DC (type test)
Ambient conditions
Ambient temperature during operation
● horizontal installation, min.-25 °C; From FS03
● horizontal installation, max.60 °C
● vertical installation, min.-25 °C; From FS03
● vertical installation, max.40 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max.5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Dimensions
Width25 mm
Height147 mm
Depth129 mm
Weights
Weight, approx.250 g
Other
Note:Supplied incl. 40-pole push-in front connectors. Additional basic error and noise for integration time = 2.5 ms: Voltage: ±250 mV (±0.02%), ±80 mV (±0.05%), ±50 mV (±0.05%); resistance: 150 Ohms (±0.02%); resistance thermometer: Pt100 climate: ±0.08 K, Ni100 climate: ±0.08 K; thermoelement: Type B, R, S: ±3 K, type E, J, K, N, T: ±1 K
Weight0.410 kg
Dimensions15.4 × 25.6 × 3.4 cm

Title

Go to Top