SIRIUS – 3RV5 – 3 Poles S2 Circuit Breakers – Siemens Circuit Breakers

USD $ 91.14USD $ 119.07

SKU: N/A

Specifications

Part number3RV5031-4DA103RV5031-4EA103RV5031-4FA103RV5031-4GA103RV5031-4HA10
product brand name SIRIUS SIRIUS SIRIUS SIRIUS SIRIUS
product designationCircuit breakerCircuit breakerCircuit breakerCircuit breakerCircuit breaker
design of the productfor motor protectionfor motor protectionfor motor protectionfor motor protectionfor motor protection
product type designation3RV53RV53RV53RV53RV5
General technical data
size of the circuit-breakerS2S2S2S2S2
power loss [W] total typical12 W15 W20 W20 W20 W
insulation voltage with degree of pollution 3 at AC rated value690 V690 V690 V690 V690 V
surge voltage resistance rated value6 kV6 kV6 kV6 kV6 kV
shock resistance according to IEC 60068-2-2725g / 11 ms25g / 11 ms25g / 11 ms25g / 11 ms25g / 11 ms
Substance Prohibitance (Date)7/1/20067/1/20067/1/20067/1/20067/1/2006
Ambient conditions
installation altitude at height above sea level maximum2 000 m2 000 m2 000 m2 000 m2 000 m
ambient temperature
? during operation-20 … +60 °C-20 … +60 °C-20 … +60 °C-20 … +60 °C-20 … +60 °C
? during transport-50 … +80 °C-50 … +80 °C-50 … +80 °C-50 … +80 °C-50 … +80 °C
relative humidity during operation10 … 95 %10 … 95 %10 … 95 %10 … 95 %10 … 95 %
Main circuit
number of poles for main current circuit33333
adjustable current response value current of the current-dependent overload release18 … 25 A22 … 32 A28 … 40 A36 … 45 A40 … 50 A
operating voltage
rated value690 V690 V690 V690 V690 V
at AC-3 rated value maximum690 V690 V690 V690 V690 V
operating frequency rated value50 … 60 Hz50 … 60 Hz50 … 60 Hz50 … 60 Hz50 … 60 Hz
operational current rated value 25 A25 A32 A40 A45 A50 A
operational current at AC-3 at 400 V rated value25 A32 A40 A45 A50 A
operating frequency at AC-3 maximum15 1/h15 1/h15 1/h15 1/h15 1/h
Protective and monitoring functions
trip classCLASS 10CLASS 10CLASS 10CLASS 10CLASS 10
design of the overload releasethermalthermalthermalthermalthermal
maximum short-circuit current breaking capacity (Icu) at AC at 400 V rated value50 kA50 kA50 kA50 kA50 kA
operating short-circuit current breaking capacity (Ics) at AC at 400 V rated value25 kA25 kA25 kA25 kA25 kA
response value current of instantaneous short-circuit trip unit325 A416 A520 A585 A650 A
Short-circuit protection
product function short circuit protectionYesYesYesYesYes
design of the short-circuit tripmagneticmagneticmagneticmagneticmagnetic
Installation/ mounting/ dimensions
mounting positionanyanyanyanyany
fastening methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN50022screw and snap-on mounting onto 35 mm DIN rail according to DIN EN50022screw and snap-on mounting onto 35 mm DIN rail according to DIN EN50022screw and snap-on mounting onto 35 mm DIN rail according to DIN EN50022screw and snap-on mounting onto 35 mm DIN rail according to DIN EN50022
height140 mm140 mm140 mm140 mm140 mm
width55 mm55 mm55 mm55 mm55 mm
depth149 mm149 mm149 mm149 mm149 mm
required spacing for grounded parts
forwards140 mm140 mm140 mm140 mm140 mm
backwards0 mm0 mm0 mm0 mm0 mm
upwards50 mm50 mm50 mm50 mm50 mm
at the side30 mm30 mm30 mm30 mm30 mm
downwards50 mm50 mm50 mm50 mm50 mm
Connections/ Terminals
type of electrical connection
for main current circuitscrew-type terminals with box terminalsscrew-type terminals with box terminalsscrew-type terminals with box terminalsscrew-type terminals with box terminalsscrew-type terminals with box terminals
arrangement of electrical connectors for main current circuitTop and bottomTop and bottomTop and bottomTop and bottomTop and bottom
type of connectable conductor cross-sections
for main contacts
— solid or stranded2x (0.75 … 25 mm²), 1x (0.75 … 35 mm²)2x (0.75 … 25 mm²), 1x (0.75 … 35 mm²)2x (0.75 … 25 mm²), 1x (0.75 … 35 mm²)2x (0.75 … 25 mm²), 1x (0.75 … 35 mm²)2x (0.75 … 25 mm²), 1x (0.75 … 35 mm²)
— finely stranded with core end processing2x (0.75 … 16 mm²), 1x (0.75 … 25 mm²)2x (0.75 … 16 mm²), 1x (0.75 … 25 mm²)2x (0.75 … 16 mm²), 1x (0.75 … 25 mm²)2x (0.75 … 16 mm²), 1x (0.75 … 25 mm²)2x (0.75 … 16 mm²), 1x (0.75 … 25 mm²)
at AWG cables for main contacts2x (18 … 2), 1x (18 … 2)2x (18 … 2), 1x (18 … 2)2x (18 … 2), 1x (18 … 2)2x (18 … 2), 1x (18 … 2)2x (18 … 2), 1x (18 … 2)
tightening torque
for main contacts with screw-type terminals3 … 4.5 N·m3 … 4.5 N·m3 … 4.5 N·m3 … 4.5 N·m3 … 4.5 N·m
Safety related data
protection class IP on the front according to IEC 60529IP20IP20IP20IP20IP20
touch protection on the front according to IEC 60529finger-safe, for vertical contact from the frontfinger-safe, for vertical contact from the frontfinger-safe, for vertical contact from the frontfinger-safe, for vertical contact from the frontfinger-safe, for vertical contact from the front
WeightN/A
DimensionsN/A

Title